Serving Arizona school districts since 1999 480-460-5199 info@needthese.com
NeedThese, Your Tech-ucation Partner Your quote

Products › Power & Rack Equipment

APC BY SCHNEIDER ELECTRIC

APC AP7801B power distribution unit (PDU) 8 AC outlet(s) 1U Black

Part number AP7801B

RACK PDU METERED 120V 20A 1U 8X5-20

Manufacturer
APC BY SCHNEIDER ELECTRIC
Part number
AP7801B
Condition
New
Category
Power & Rack Equipment › Power Equipment
1GPA category
Hardware

Overview

Availability

Alarm Thresholds

Define alarm thresholds in order to avoid overloaded circuits. Network and visual alarms inform the user of possible problems. (Note: Only available on units with the current monitoring capabilities. Please see SKU specifications for availability)

Local Current Monitoring Display

The aggregate current draw per rack PDU is displayed on the unit via a digital display. The local digital display helps installers avoid overloaded circuits by providing a visible warning when the current draw is close to the maximum amperage draw of the strip. (Available on designated SKUs only)

Integrates with StruxureWare Data Center Expert

An IT-ready, scalable access monitoring system that collects, organizes, and distributes critical alerts, surveillance video and key information, providing a unified view of complex physical infrastructure environments from anywhere on the network

Load indicator LED

Indicates overload and warning conditions based on the user-defined alarm thresholds. Alerts users of potential overloaded circuits.

Flash Upgradeable

Quickly and easily upgrade firmware via network download for future product enhancements. Eliminates the need to replace products already installed in the field when new features are released. (Note: Networked units only)

Remote Management Capabilities

Full-featured network management interfaces that provide standards-based management via Web, SNMP, and Telnet. Allows users to access, configure, and manage units from remote locations to save valuable time. Associated with this feature is the ability to quickly and easily upgrade the firmware via network download to installed units for future product enhancements.

Agility

Rack-Mountable

Includes horizontal, vertical, and toolless-mount varieties. Puts power where it is needed most - in the racks near the equipment.

Single input power source

Supply power from one branch whip to multiple pieces of equipment, conveniently powering rack-mount equipment. Saves time and money during installation by using one branch whip and standard connections.

Wide range of input and output connections

Product family includes a variety of input and output connections to distribute 120V, 208V, or 230V power to multiple outlets. Having a variety of inputs and outputs allow users to adapt to varying power requirements. APC offers units that bring up to 14.4kW using a single branch whip.

Marketing Features

Load indicator LED

Indicates overload and warning conditions based on the user-defined alarm thresholds. Alerts users of potential overloaded circuits.

Local Current Monitoring Display

The aggregate current draw per power distribution unit is displayed on the unit via a digital display. The local digital display helps installers avoid overloaded circuits by providing a visible warning when the current draw is close to the maximum amperage draw of the strip.

Local and web-based monitoring

Status available to customers both in the data center and remotely

Wide range of input and output connections

Product family includes a variety of input and output connections to distribute 120V, 208V, or 230V power to multiple outlets. Having a variety of inputs and outputs allow users to adapt to varying power requirements. APC offers units that bring up to 14.4kW using a single branch whip.

Alarm Thresholds

Specifications

Design
PDU typesMetered
Rack capacity1U
Product colourBlack
Ports & interfaces
AC outlets quantity8 AC outlet(s)
AC outlet typesNEMA L5-20R
Input connection typeNEMA L5-20P
Features
LED indicatorsYes
Cable length3.66 m
Management features
MonitoringCurrent
Power
Nominal input voltage100-120 V
AC input frequency50 - 60 Hz
Maximum current20 A
Nominal output voltage120 V
Load capacity1920 VA
Maximum input current per phase20 A
Maximum total current draw per phase16 A
Certificates
Compliance certificatesRoHS
CertificationcUL, CSA, FCC 15 A, ICES-003, UL 60950, UL
Operational conditions
Operating temperature (T-T)-5 - 45 °C
Storage temperature (T-T)-25 - 65 °C
Operating relative humidity (H-H)5 - 95%
Storage relative humidity (H-H)5 - 95%
Operating altitude0 - 3000 m
Non-operating altitude0 - 15000 m
Weight & dimensions
Width444 mm
Depth102 mm
Height44 mm
Weight1.73 kg
Packaging data
Package weight2.91 kg
Package width470 mm
Package depth337 mm
Package height64 mm

Product photos and overview provided by the manufacturer through Icecat. Confirm specifications with your rep before ordering.